Elektrogas Manual Reset Solenoid Valve for Gas – EVRM-NC-12

Brand: Elektrogas

Model: EVRM-NC-912

Dimensions
Width 700.00
Height 786.00
Length 460.00

£3,442.50 £9,667.36
Price Ex Vat: £2,868.75

1 in stock

Description

12 inch DN300 flange gas safety shut off solenoid valve with manual reset Elektrogas EVRM-NC-912
Function: 2/2 way normally closed with manual reset
Operation: direct acting
Port: 12 DN300 PN16 flange.
Body: Aluminium
Seals: NBR based rubber certified for gas (EN549)
Closing time: < 1 second
Certified: EN161 Class A Group 2, CE Reg PED/0497/895/07, PED 2014/68/EU (Pressure Equipment Directive), ATEX 2014/34/EU, electromagnet compatibility 2014/30/EU, low voltage directive 2014/35/EU and RoHSII 2011/65/EU.
Pressure: 0 to 600 milliBar, option (EVRM6NC) 6 Bar
Media: Air and Natural Gas and non corrosive gases families 1, 2 and 3 (EN437), option (J) Biogas free of ferrous metals with FPM sealing.
Kvs flow factor: 1020 cubic meters an hour
Voltage: 230vAC is standard, option (D) 12vAC/DC, (C) 24vAC/DC or (B)110vAC
Coil: 12 Watt 100% duty rated Class F with IP54 terminal box (voltage tolerance -15% to +10%
Coil option: ATEX for use in zones 2 and 22 according to 2014/34/EU ATEX directive. Category II 3 G,D, protection Ex nA IIA T4 Gc X, Ex Tc IIIB T135C Dc X or Ex Tc IIIC T135C Dc X (IP65)
Filter: Incoroprated 600 μm (0,02 in) metal meshfilter to protect valve disc and seals as well as downstream components.
Gauge ports: provided with G1/4 pressure gauge ports on both sides to connect manometers, pressure switches, leak tester or other gas equipment.
Position indication: provided G1/8 connection to fit CPI closed position switch or indicator.

The EVRM-NC valve is a manual reset safety valve that is normally closed. When not in working position the spring presses shutter closed preventing gas flow. Simply by energizing the coil the valve will not open. It is necessary to manually lift the reset rod located at the top of the coil. Once opened, the valve can maintain this open position whilst electric current is applied to the coil. In absence of electric current the valve closes rapidly (under 1 second) and remains shut until the reset proceedure is reapplied. Once the causes for the lock have been eliminated, valve must be opened manually as described above.

Models DN125-DN300 and 6 Bar versions are provided with a dual-shutter pressure compensation system. To open the valve pull the knob for the first step, wait for pressure compensation, and then pull the knob completely up to full resetting.

All components are designed to withstand any mechanical, chemical and thermal condition occuring during typical service. Effective impregnation and surface treatments have been used to improve mechanical reliability , sealing and corrosion resistance.

Valves are 100% tested by computer test machines and are fully warrented.

Equivalent To

Costa, Madas gas valve, GCR8300, GCR4300, GCR2300, GSSV300, M16/RM NC DN300
EVRMNC912

Add a review of this product